Manufacturer: Voltaris

Circuit breaker type B 20 A

Voltaris 20 A type B single-pole miniature circuit breaker with a 6 kA breaking capacity, for consumer units and distribution boards on 35 mm DIN rail. Protects circuits against overload and short circuit, with a clear on and off toggle and a contact indicator on the front.
SKU: VT-MCB20
In stock
Availability: In stock
Price
$4.45

PRICE BREAKS - The more you buy, the more you save

Quantity Unit price
10–49 $4.23
50–199 $4.00
200+ $3.78

Description

Overview

A miniature circuit breaker protects a circuit's cables against overload and short circuit, and it can be reset once the cause has been put right. This single-pole breaker is type B, which trips magnetically at three to five times its rating. That makes it the usual choice for domestic and commercial circuits with mainly resistive and lighting loads.

Each breaker is one module wide, 18 mm, and clips onto a 35 mm DIN rail. The rating is printed on the front and the toggle can be locked in the off position with a lock-off device, sold separately.

Where to use it

Use these breakers in consumer units and distribution boards designed for single-pole DIN-rail devices.

  • Lighting circuits in homes and offices
  • Ring final and radial socket circuits
  • Immersion heaters, cookers and showers
  • Sub-circuits in commercial distribution boards
  • Replacing failed breakers of the same type and rating

Choosing the right rating

The breaker must be rated no higher than the current the circuit's cable can carry, and at least as high as the design current. As a guide, 6 A suits lighting circuits, 10 A suits larger lighting circuits and fans, 16 A suits immersion heaters and small radials, 20 A suits radial socket circuits in 2.5 mm² cable, 32 A suits ring final circuits and larger radials, and 40 A suits cookers and many electric showers.

Always confirm the rating from the circuit design and the earth fault loop impedance limits in BS 7671. Type B breakers need a lower loop impedance than type C to disconnect in time.

Design and construction

Inside the breaker, a bimetal strip responds to overloads and an electromagnetic coil responds to short circuits. An arc chute splits and cools the arc when the contacts open, which gives the breaker its 6000 A breaking capacity and energy limiting class 3. The housing is flame-retardant thermoplastic.

The terminals are rising-cage clamps that take cables up to 25 mm² and a pin-type busbar at the same time. A contact position indicator shows red when the contacts are closed and green when they are open.

Installation and care

Isolate the board at the main switch and prove it dead. Clip the breaker onto the rail, insert the busbar pin and tighten the terminal to the torque given in the specifications. Connect the circuit's line conductor to the outgoing terminal and label the circuit on the board schedule.

Exercise the breaker by switching it off and on during periodic inspection. If it trips repeatedly, investigate the circuit rather than fitting a larger rating.

  • Fit only in boards designed for this breaker format
  • Check the busbar type before ordering
  • Work on consumer units must be done by a competent person

Compliance and ordering

The breakers are made to BS EN 60898-1 and are CE and UKCA marked. They come boxed singly with the rating on the end label, so they are easy to pick from a store. Contractors can order a mix of ratings in one quick order and keep a saved list for van stock.

Demo product: invented for the Cartenvo B2B demo store.

Technical specifications

Specifications

Products specifications

Attribute name Attribute value
Type MCB type B
Rating (A) 20
General
Brand Voltaris
Product type Miniature circuit breaker, single pole
Application Consumer units and distribution boards
Country of manufacture France
Warranty 5 years
Performance
Reference temperature (°C) 30
Operating temperature (°C) -25 to +55
Mechanical life (operations) 20,000
Electrical life (operations) 10,000
Electrical
Rated voltage (V) 230/400 AC
Poles 1
Breaking capacity (A) 6000
Magnetic trip range 3 to 5 × rated current
Energy limiting class 3
Typical circuit Radial sockets
Terminal capacity (mm²) Up to 25
Terminal torque (Nm) 2.0
Dimensions and weight
Width (modules) 1 (18 mm)
Dimensions (L × W × H, mm) 85 × 18 × 72
Net weight (kg) 0.11
Materials and construction
Housing Flame-retardant thermoplastic, white
Busbar compatibility Pin-type busbar
Mounting 35 mm DIN rail
Compliance and safety
Standards BS EN 60898-1
Contact position indicator Yes, red on and green off
CE / UKCA marked Yes
RoHS compliant Yes
Packaging and ordering
Pack quantity 1
Barcode type EAN-13

FAQs

Will this breaker fit my consumer unit?

It fits boards designed for 18 mm single-pole DIN-rail breakers with a pin-type busbar. Breakers from different makers vary in shape and busbar connection, so mixing brands in one board is not recommended and may affect the board's certification.

What is the difference between type B and type C?

A type B breaker trips magnetically at three to five times its rating, and a type C at five to ten times. Type B suits most domestic and commercial circuits; type C suits circuits with motors or large inrush currents, such as some lighting banks and workshop machines.

Which rating do I need for a ring final circuit?

A ring final circuit in 2.5 mm² twin and earth is normally protected by a 32 A breaker. The final choice depends on the installation method and must be confirmed by the circuit design.

Does this breaker give RCD protection?

No. A miniature circuit breaker protects against overload and short circuit only. For protection against earth leakage, the circuit needs an RCD or an RCBO.

My breaker keeps tripping. Should I fit a larger one?

No. Repeated tripping means the circuit is overloaded or has a fault. Find and fix the cause; a larger breaker could let the cable overheat.

Can I order breakers in mixed ratings?

Yes. Each rating is a separate SKU, so you can add the quantities you need through quick order and save the list for restocking your van.